Basic specifications
Project specifications
Power supply voltage AC power supply 100-240 V AC 50/60 Hz
AC/DC power supply 10-24V AC 50/60 Hz; 10-24V DC
Power consumption of AC power supply below 7 VA
AC/DC power supply AC: below 6 VA; DC: Below 5W
The allowable voltage variation range is 90%~110% of the power supply voltage
Insulation resistance ≥ 100M Ω (500V DC MEGA reference)
Insulation strength 2000V AC (test conditions: 50/60Hz, 1 minute)
Anti interference IEC61000-4-2 (electrostatic discharge), Class III
IEC61000-4-4 (Electrical Fast Transient Pulse Group), Class III
IEC61000-4-5 (surge), Class III
Protection level IP65 (product front panel protection) (GB/T42-2008)
Operating environment temperature -30~60 ºC (storage: -40~65 ºC)
Environmental humidity of 35-85% R • H, no condensation
Installation location indoor, height < 2000m
Input specifications
Project specifications
Measurement control speed 5/20/60/100/200 times/second optional
When the basic error measurement and control speed is 5 times/second, the error is less than ± 0.05% F • S
(The faster the measurement and control speed, the greater the error)
Display range -99999~99999, resolution 1/10000
Display specifications: 6-digit LED display
Analog input signal type
Project measurement scope
The specification range of potentiometer W resistance value is 0.5~100k Ω, which is acceptable
Optional specifications
Project specifications
Alarm
Output 160 × 80 size T1~T4 1-4 alarm relay outputs, both normally open and normally closed dual contact 250V AC/3A
Resistive load
96 × 48 size T1~T2 1-2 point alarm relay output, both normally open and normally closed dual contacts
T3 3-point alarm relay output, single normally open contact
K1 1-point input
(When selecting K1, communication and transmission can only be selected as either option)
Analog output A1 current output (4-20) mA, (0-10) mA, (0-20) mA photoelectric isolation, resolution: 1/3000, load capacity: 600 Ω
A2 voltage output (0-5) V, (1-5) V
A3 voltage output (0-10) V